Version | Power supply, switch-mode power supply unit, 24 V |
Order No. | 1469560000 |
Type | PRO ECO3 960W 24V 40A |
GTIN (EAN) | 4050118275728 |
Qty. | 1 pc(s). |
Depth | 120 mm |
Depth (inches) | 4.724 inch |
Height | 125 mm |
Height (inches) | 4.921 inch |
Width | 160 mm |
Width (inches) | 6.299 inch |
Net weight | 2,899 g |
Storage temperature | -40 °C...85 °C |
Operating temperature | -25 °C...70 °C |
RoHS Compliance Status | Compliant with exemption |
RoHS Exemption (if applicable/known) | 7a, 7cI |
REACH SVHC | Lead 7439-92-1 |
SCIP | 6d8cdf22-8230-4af8-86c8-3558c716666d |
Certificate No. (cURus) | E255651 |
AC input voltage range | 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC | ||||||||||||||||||||||||||
Connection system | Screw connection | ||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
DC input voltage range | 450...800 V DC | ||||||||||||||||||||||||||
Frequency range AC | 47...63 Hz | ||||||||||||||||||||||||||
Input frequency | 47...63 Hz | ||||||||||||||||||||||||||
Input fuse (internal) | Yes | ||||||||||||||||||||||||||
Inrush current | max. 40 A | ||||||||||||||||||||||||||
Nominal power consumption | 1,067 VA | ||||||||||||||||||||||||||
Rated input voltage | 3x 400...3x 500 V AC (wide-range input) | ||||||||||||||||||||||||||
Recommended back-up fuse | 6 A / DI, safety fuse 10 A, Char. B, circuit breaker 6...8 A, Char, C, circuit breaker | ||||||||||||||||||||||||||
Surge protection | Varistor |
Capacitive load | unrestricted |
Connection system | Screw connection |
Continuous output current @ UNominal | 40 A @ 50 °C, 24 A @ 70 °C |
Nominal output current for Unom | 40 A @ 50 °C |
Output power | 960 W |
Output voltage, max. | 28 V |
Output voltage, min. | 22 V |
Output voltage, note | (adjustable via potentiometer) |
Overload protection | Yes |
Parallel connection option | yes, max. 3 |
Protection against inverse voltage | Yes |
Ramp-up time | ≤ 100 ms |
Rated output voltage | 24 V DC ± 1 % |
Residual ripple, breaking spikes | <50 mVPP @ 24 V DC, IN |
AC failure bridging time @ Inom | > 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V AC | ||||||||||||||||||||||||||
Degree of efficiency | 90% | ||||||||||||||||||||||||||
Earth leakage current, max. | 3.5 mA | ||||||||||||||||||||||||||
Housing version | Metal, corrosion resistant | ||||||||||||||||||||||||||
Indication | Green LED (Uoutput > 21.6 V DC), Yellow LED (loutput > 90 % IRated typ. ), red LED (overload, overtemperature, short-circuit, Uoutput <20.4 V DC) | ||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
Max. perm. air humidity (operational) | 5 %…95 % RH | ||||||||||||||||||||||||||
Mounting position, installation notice | on terminal rail TS 35 | ||||||||||||||||||||||||||
Power factor (approx.) | > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC | ||||||||||||||||||||||||||
Power loss, idling | 5 W | ||||||||||||||||||||||||||
Power loss, nominal load | 95 W | ||||||||||||||||||||||||||
Protection against over-heating | Yes | ||||||||||||||||||||||||||
Protection degree | IP20 | ||||||||||||||||||||||||||
Short-circuit protection | Yes | ||||||||||||||||||||||||||
Surge voltage category | II |