Version | Power supply, switch-mode power supply unit, 24 V |
Order No. | 1478130000 |
Type | PRO MAX 240W 24V 10A |
GTIN (EAN) | 4050118286052 |
Qty. | 1 pc(s). |
Depth | 125 mm |
Depth (inches) | 4.921 inch |
Height | 130 mm |
Height (inches) | 5.118 inch |
Width | 60 mm |
Width (inches) | 2.362 inch |
Net weight | 1,050 g |
Storage temperature | -40 °C...85 °C |
Operating temperature | -25 °C...70 °C |
Humidity at operating temperature | 5...95 %, no condensation |
RoHS Compliance Status | Compliant with exemption |
RoHS Exemption (if applicable/known) | 7a, 7cI |
REACH SVHC | Lead 7439-92-1 |
SCIP | 6d8cdf22-8230-4af8-86c8-3558c716666d |
Certificate No. (cURus) | E255651 |
AC input voltage range | 85…277 V AC | ||||||||||||||
Connection system | Screw connection | ||||||||||||||
| |||||||||||||||
DC input voltage range | 80...370 V DC | ||||||||||||||
Frequency range AC | 45…65 Hz | ||||||||||||||
Input fuse (internal) | Yes | ||||||||||||||
Inrush current | max. 15 A | ||||||||||||||
Nominal power consumption | 262.3 VA | ||||||||||||||
| |||||||||||||||
Rated input voltage | 100...240 V AC | ||||||||||||||
Recommended back-up fuse | 10 A, Char. B circuit breaker, 6...8 A, char. C circuit breaker | ||||||||||||||
Surge protection | Varistor |
Connection system | Screw connection |
Continuous output current @ UNominal | 12 A @ 45°C, 7,5 A @ 70°C |
Nominal output current for Unom | 10 A @ 60 °C |
Output power | 240 W |
Output voltage, max. | 29.5 V |
Output voltage, min. | 22.5 V |
Output voltage, note | (adjustable via potentiometer) |
Parallel connection option | yes, max. 5 |
Protection against inverse voltage | Yes |
Rated output voltage | 24 V DC ± 1 % |
Residual ripple, breaking spikes | <50 mVss @ UNenn, Full Load |
AC failure bridging time @ Inom | min. 20 ms | ||||||||||||||
Current limiting | > 120% IN | ||||||||||||||
Degree of efficiency | 91.5% | ||||||||||||||
Derating | > 60°C / 75% @ 70°C | ||||||||||||||
Earth leakage current, max. | 3.5 mA | ||||||||||||||
Housing version | Metal, corrosion resistant | ||||||||||||||
| |||||||||||||||
Mounting position, installation notice | Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. | ||||||||||||||
Power loss, idling | 2.4 W | ||||||||||||||
Power loss, nominal load | 22.3 W | ||||||||||||||
Protection against reverse voltages from the load | 30…35 V DC | ||||||||||||||
Protection degree | IP20 | ||||||||||||||
Short-circuit protection | Yes | ||||||||||||||
Start-up | ≥ -40 °C | ||||||||||||||
Status indication | LED red/green and relay (≥21.6 V DC LED green, relay on/ ≤20.6 LED red, relay off) | ||||||||||||||
Surge voltage category | III |